Wcc3.exe screen descriptions, Override screen override screen – WattMaster WM-WCC3-TGD-01B User Manual

Page 205

Advertising
background image

WCC III Technical Guide

3-91

WCC3.EXE SCREEN DESCRIPTIONS

OVERRIDE

SCHEDULES

Starting End

ADDRESS

Type/Value TIME MONTH

DAY

TIME MONTH

DAY

W12

Off

745

2

15

845

2

15

S5

Off

745

2

15

845

2

15

GB9

On

745

2

15

845

2

15

GA15

72.5 Deg F

950 2

16

1200 2

17

GA10 30.0

Deg

F 1130 3

17

2200 3

18

184K2C

Schd

On 900

4

11

1500 4

14

HOME for menu

OVERRIDE SCREEN

Override Screen

This screen allows you to override addresses within the system for
programmable time periods. The allowable choices for override
type depend on the password level.

With Level 1 Password, choices are <Schd On, Schd Off>
With Level 2 Password, choices are <SchdON, SchdOff>
With Level 3 Password, choices are <ALL>

ADDRESS

This is a user entered fi eld which initiates the Override program of
the WCC III system. Addresses which may be used on this screen
are shown below:

# = Satellite address number

#An - Analog Input (n = 1 to 8)

#Pn - Analog Output (n = 1 to 8)

#KnH - Control Output (H Contact) (n = 1 to 8)

#KnC - Control Output (C contact) (n = 1 to 8)

Wn - Week Schedule (n = 1 to 128)

Sn - Optimal Start (n = 1 to 64)

GBn - Binary Global (n = 1 to 512)

GAn - Analog Global (n = 1 to 256)

#RnA - Data Register (n = 1 to 8)

#RnB - Data Register (n = 1 to 8)

#Cn - Comparator (n = 1 to 8)

#On - Binary Out (n = 1 to 16)

#Ln - Binary Input (n = 1 to 16)

Type/Value

The Type or Value of the address is entered in this position. A
binary type of address will have a type of either being ON or OFF.
An analog address will have a numerical value such as °F, PSI,
KW, % Sun, etc.

-----

Starting -----

----- End -----

The Start and End portion of the program is where you enter the
Time, Month, and Day for the override to occur. The override will
erase itself from the screen after the override has been completed.

Clear Structure

Select

<Clear Structure>

from the Action Menu or select the

Clear Structure icon to clear the values from the screen.

NOTE:

Values entered may remain after you clear the

structure until you leave the screen and return to the Main

Menu and then open the Override Screen again.

Advertising