Wcc3.exe screen descriptions, Analog global summary screen – WattMaster WM-WCC3-TGD-01B User Manual

Page 240

Advertising
background image

WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-126

ANALOG

Specifi es the summary type to be displayed. Because this is a
“choice” fi eld, the list of available choices will be displayed at the
bottom of the screen:

<ANALOG, BINARY>

To make your selection, press the

<space bar>

once for each

choice until the desired summary type has been selected and then
press

<Enter>

. (If you select a summary type that is different than

that currently being displayed, the screen will be rewritten with the
appropriate screen information.)

To view or edit a specifi c analog global, use the arrow keys to
position the cursor (shown as “>” along the left-hand side of the
screen) to the desired point and press

<Enter>

. The Analog Global

Screen for the specifi ed point will now appear.

Time / Date

The present time and date will automatically appear at these
locations.

Description

The description message which was entered on the Analog Global
Screen
is displayed here to aid you in identifying the different
analog globals within the screen.

ANALOG GLOBAL SUMMARY SCREEN


ANALOG

Global

Summary

GA

1

Time

Date

8:38

1/21

Description

Value

Alarm

Limits

Alarm

Time

GA1 : Linux Primary Global

55.0 Deg F 25.0 75.0

GA2 : Linux Global

65.0 Deg F 25.0 75.0

GA3 : Linux Global

44.0 Deg F 25.0 75.0

GA4 : Linux Global

55.0 Deg F 25.0 75.0

GA5 : Linux Global

66.0 Deg F 25.0 75.0

GA6 : Linux Global

55.0 Deg F 25.0 75.0

GA7 : Linux Global

55.0 Deg F 25.0 75.0

GA8 : Linux Global

55.0 Deg F 25.0 75.0

GA9 : Linux Global

55.0 Deg F 25.0 75.0

GA10: Linux Global

1.0 Deg F 25.0 75.0

15:40 01/16

GA11: Linux Global

999.9 Deg F 25.0 75.0

15:40 01/16

GA12: Linux Global

55.0 Deg F 25.0 75.0

GA13: Linux Global

55.0 Deg F 25.0 75.0

GA14: Linux Global

55.0 Deg F 25.0 75.0

15:40 01/16

GA15: Linux Global

99.0 Deg F 25.0 75.0

GA16: Linux Global

55.0 Deg F 25.0 75.0

GA17: Linux Global

55.0 Deg F 25.0 75.0

GA18: Linux Global

55.0 Deg F 25.0 75.0

Value

The present value of the global analog is displayed on the screen
at this location.

Alarm Limits Alarm Time

The alarm limits for the global analog are shown here along with
the time that the alarm occurred.

However, if a global alarm is active, the alarm class will appear on
the Main Menu after the “Active alarms in classes:” statement. The
alarm will also show on the Alarm Summary Screen.

Acknowledge Alarms

The global analog alarms are acknowledged from the Global
Analog Summary Screen
by moving the cursor to the active alarm
and selecting

<Action>

from the Top Menu Bar and then selecting

<Acknowledge Alarm>

. If the global analog value is within the

alarm limits, the alarm message will be cleared from the screen.
It can take up to 30 seconds before the alarm is cleared from the
screen.

Analog Global Screen’s WCC III Logical Address is GAXXX, where GA = Global Analog and XXX = Global Analog Address

Analog Global Summary Screen