12. WCC III INSTALLATION

GUIDE

WCC III Technical Guide

12-1

SECTION 12:

WCC III INSTALLATION GUIDE

__________________________________________

WCC III System Requirements

To accomplish remote communications via the internet, the
following items are needed in addition to the WCC III system in
order to control the building mechanical systems. The WCC III
system is not to be used in any application where Fire/Life/Safety
is an issue.

WCC III – MCD System Requirements

(On-Site WCC III – MCD Computer):

DSL, or a Cable router/switch that connects to the
internet. Or, as an alternative, an internal jobsite
IP network that does not connect to the internet,
but when using this internal jobsite IP network, the
external internet Email of alarms from the WCC III
- MCD will not be possible. Also, external access
via the internet may not be possible.

A fi xed static IP address or a fi xed IP domain host
name.

Enabled port forwarding on the Firewall of the
router/switch. This is only if a fi rewall is used.

On earlier versions, antivirus software is initially
provided by WattMaster Controls, with Norton
antivirus software for a period of 1 year. The
customer must maintain the antivirus software after
this 1-year period. Later versions are shipped with
Linux as the operating system and do not require
anti-virus software.

An Email address that supports a SMTP
server for SENDING with a pop server for
RECEIVING Emails, and it must have “auth
login” authentication. TLS or SSL modes are not
supported. WattMaster Controls can provide an
Email address with these requirements.

An Uninterruptible Power Supply (UPS) – 750-
Watt minimum

A wall mounting surface is preferred.

A dedicated 120VAC power circuit is required.

Front End Software Requirements

(Operator Console Software):

A Microsoft Windows XP /Vista/Windows 7-based
computer.

Minimum hardware specifi cation for the Microsoft
Windows XP / Vista based computer is a Pentium
IV running at 2.4 Giga Hertz with at least 1 GB
of RAM, and 10 GB of spare hard drive space. A
CDROM/DVD player is also required for software
installation.

WCC III software package – Provided on a
CDROM, or is available via a download on the
WCC Controls website: www.wcc-controls.com.
The installation CDROM contains the following
programs:

WCC III.EXE (SS5021)
WCCUTILITY.EXE (SS5023)
SCUSCR.EXE (SS5026)
WCC3Trendlog.EXE (SS5028)
TenantReport.EXE (SS5025)
TenantOverride.EXE* (SS5024)
WGCC3.EXE (SS5029)
WCC3 Download (SS5030)
WCC3 Guest (SS5022)

The CDROM part number (WattMaster Part #
DM1WC011-01X, were “X” = revision level)

A DSL or Cable router/switch that connects to the
internet, or access to the internet via some other
method. Or, as an alternative, an internal jobsite
IP network that does not connect to the internet,
but when using this internal jobsite IP network, the
external internet Email of alarms from the WCC III
- MCD may not be possible.

* NOTE:

The TenantOverride.exe program is also available

as a single program installation for the end users that are using
the simplistic graphical interface of the TenantOverride.exe
screen to locally turn on and off specifi c control points that are
applicable to the end user.