Wcc3.exe screen descriptions, Global analog - integral mode average mode screen, Analog global integral mode average mode screen – WattMaster WM-WCC3-TGD-01B User Manual

Page 249

Advertising
background image

WCC III Technical Guide

3-135

WCC3.EXE SCREEN DESCRIPTIONS

Sampling From:

The value of the global analog will be the average of this input over
the specifi ed time period.

For example, if 1A3 is input here, the system will periodically read
the value of analog input #3 on satellite controller #1. The value
of the global analog will be the average of the readings over the
specifi ed time period.

Automatically reset by GBXXX being ON

This allows you to have the system automatically restart the
averaging cycle when a global binary value goes either ON or
OFF.

Because this second fi eld is a “choice” fi eld, the list of available
choices will be displayed at the bottom of the screen:

<OFF, ON>

GLOBAL ANALOG - INTEGRAL MODE

AVERAGE MODE SCREEN

ANALOG

Global

#:

30

Name

is

GA30

Description: AVG OA TEMP

Data Pattern: x,xxx

Unit

of

Measure:

1

°F

In Local Set this global defaults to LAST VALUE
Mode

3:

Integral

Sampling from : 1A3

Automatic Reset by GB1 being ON

Sampling rate:

1 Minutes

Window: 33 days

Mode:

Average

Divisor:

1

i

=

n

Global value =

(  (Di/n ) / divisor

i

=

1

If sampling data is unavailable, then use 50 as default value

---------------Alarm---------------

Range Low Limit High Limit

Type Message #

Message

None

Reset random data by pressing Ctrl-R after editing.

HOME for menu

Make your selection by pressing the

<space bar>

once for each

choice until the desired mode type has been selected, and then
press

<Enter>

.

Sampling Rate: 1 Minutes

Window: 33 Days

Assume we are monitoring outside air temperature and 1 minute
is entered as the “sampling rate” and 33 days for the Window. The
system will read the value of the outside air temperature every
minute and then average the values until 33 days have elapsed.
After 33 days the calculation process will start over.

In the example above, GB1 goes on at the beginning of each new
month to restart the averaging process, so the end of the window is
never reached. If the end of the window is reached, the system will
restart the calculation process.

The sampling rate can vary from 1 minute to 99 hours. The window
will accept from 0-9999 minutes, hours, days, or samples.

Analog Global Screen’s WCC III Logical Address is GAXXX, where GA = Global Analog and XXX = Global Analog Address

Analog Global Integral Mode Average Mode Screen

Advertising
This manual is related to the following products: