Wcc3.exe screen descriptions, Analog global look up table screen, Analog global look up table mode screen – WattMaster WM-WCC3-TGD-01B User Manual

Page 257

Advertising
background image

WCC III Technical Guide

3-143

WCC3.EXE SCREEN DESCRIPTIONS

Analog Global #:____

Specifi es the global number and its type. Because this is a “choice”
fi eld, the list of available choices will be displayed at the bottom
of the screen:

<ANALOG, BINARY>

Make your selection by pressing the

<space bar>

once for each

choice until the desired global type has been selected, and then
press

<Enter>

. (If you select a global type that is different than

that currently being displayed, the screen will be rewritten with the
appropriate screen information.)

If you would like to edit a different global, simply position the
cursor to this fi eld by using the cursor positioning (arrow) keys,
entering the desired global number, and pressing

<Enter>

.

name is ______

Specifi es the name (point address) of this analog global. Any
changes to the global number will be refl ected in this point address
(e.g., ANALOG GLOBAL #: 28 would show GA 28 as the
name).

Description: ________________

Specifi es a short message which is displayed on Summary and Data
Entry/Editing Screens
to aid you in remembering points within the
system. You may enter up to 20 characters (control, codes, ALT
codes, and the double quote character are not allowed).

ANALOG GLOBAL

LOOK UP TABLE SCREEN

ANALOG

Global

#:

121

Name

is

GA121

Description: Temperature

Data Pattern: xxx.x

Unit

of

Measure:

1

°F

In Local Set this global defaults to LAST VALUE
Map From: 2A3
Extend Data to Next Table?: NO

Mode 5: Look Up Table

If the input data is unavailable, then use 70 as default value
IN OUT IN OUT IN OUT IN

OUT

1: 41 -> 41.5 16: 56 -> 59.5 31: 71 -> 68.0 46: 86 -> 78.0
2: 42 -> 42.5 17: 57 -> 60.3 32: 72 -> 68.5 47: 87 -> 78.7
3: 43 -> 44.5 18: 58 -> 61.0 33: 73 -> 69.0 48: 88 -> 79.7
4: 44 -> 46.5 19: 59 -> 61.5 34: 74 -> 69.5 49: 89 -> 80.7
5: 45 -> 47.5 20: 60 -> 62.0 35: 75 -> 70.0 50: 90 -> 81.7
6: 46 -> 49.0 21: 61 -> 62.5 36: 76 -> 70.6 51: 91 -> 83.0
7: 47 -> 51.5 22: 62 -> 63.0 37: 77 -> 71.3 52: 92 -> 84.0
8: 48 -> 51.8 23: 63 -> 63.5 38: 78 -> 72.0 53: 93 -> 85.3
9: 49 -> 53.0 24: 64 -> 64.0 39: 79 -> 72.5 54: 94 -> 86.5
10: 50 -> 54.0 25: 65 -> 64.8 40: 80 -> 73.0 55: 95 -> 88.0
11: 51 -> 55.0 26: 66 -> 65.5 41: 81 -> 74.0 56: 96 -> 89.5
12: 52 -> 56.3 27: 67 -> 66.0 42: 82 -> 74.5 57: 97 -> 91.0
13: 53 -> 57.0 28: 68 -> 66.3 43: 83 -> 75.3 58: 98 -> 93.0
14: 54 -> 58.0 29: 69 -> 67.0 44: 84 -> 76.0 59: 99 -> 95.5
15: 55 -> 59.0 30: 70 -> 67.3 45: 85 -> 77.0 60: 100 -> 100.0

HOME for menu

Analog Global Screen’s WCC III Logical Address is GAXXX, where GA = Global Analog and XXX = Global Analog Address

Analog Global Look Up Table Mode Screen