WCC3.EXE SCREEN DESCRIPTIONS

WCC III Technical Guide

3-72

Current run time: _____ seconds

This is the current accumulated run time. You may select the
units of time by positioning the cursor after the current run time.
Because this is a “choice” fi eld, the list of available choices will be
displayed at the bottom of the screen:

<Hours, Seconds, Minutes>

Make your selection by pressing the

<space bar>

once for each

choice until the desired state has been selected, and then press

<Enter>.

Starting at:

00:00 on 00/00

Specifi es the time and date that the trend log recording should
begin. (The time is represented in 24-hour format.) The system
considers *’s in these positions to be “wild cards.” Therefore, if
you want the system to log the run time independent of the time
and date, enter “*:* on */*.”

Reset by _______ being ____.

Specifi es the [binary] point address that will be used to reset (or
clear) the record trend log data. The fi rst fi eld specifi es the point
address, and the second specifi es the state or condition that the point
address needs to be in to clear the data. Because this second fi eld
is a “choice” fi eld, the list of available choices will be displayed at
the bottom of the screen:

<OFF, ON>

Make your selection by pressing the

<space bar>

once for each

choice until the desired state has been selected, and then press

<Enter>

.

Alarm Type: _____

Specifi es the priority (or “importance level”) for any alarms
generated by this input. Alarm types range from one (high priority)
to eight (low priority). The system responds to higher priority
alarms fi rst.

Alarm Message #: _____

Specifi es a message number for the run time alarm condition. This
number is used by the system to reference a textual message which
is displayed on the Alarm Summary Screen.

Alarm Limit: ____ seconds

Specifi es a time limit at which point an alarm will be activated. That
is, when the total run time exceeds this limit, an alarm indication
will be sent from the satellite. The units of time will be the same as
that selected for the current run time.