Controller inputs and outputs – WattMaster WM-WCC3-TGD-01B User Manual

Page 774

Advertising
background image

VAV/Zone Controller Technical Guide

Operator Interface

6

3 Stage Heating Applications

If three stages of electric heat are confi gured, relays #2 and #3 will stage
in a staggered sequence. This allows you to achieve 3 stages of heating
using only relays #2 and #3. Each of the 3 heating elements should be
sized for ⅓ of the total KW output required. Both the 2nd and 3rd stage
heating contactors (C2 & C3) must be connected to Relay Output #3.
See Table 1 for relay sequencing information.

Stage No.

Relay Output #2

Relay Output #3

#1

ON (C1)

OFF (C2 & C3)

#2

OFF (C1)

ON (C2 & C3)

#3

ON (C1)

ON (C2 &C3)

Table 1: Relay Sequencing For 3 Stage Heating

24 VDC Power Terminals (+V & GND)

These terminals can supply 24 Volts DC for a 24 VDC hot water valve
actuator if desired. This output is rated at 12 Watts maximum load.

Analog Output

If you are using hot water or steam heating via a modulating steam
or hot water valve, this output can supply a 0-10 Volts DC signal for
proportional control of the valve.

Controller Inputs and Outputs

Advertising
This manual is related to the following products: