Single-axis controllers, Warnings – Lenze 9400 Manual User Manual

Page 102

Advertising
background image

Single-axis controllers

Wiring

Safety notes for the installation according to U

L

or U

R

4

102

EDS94SPP101 EN 7.1

Device size 8S ... 10

Warnings!

ƒ

Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than

100000 rms symmetrical amperes, 500 V max., when protected by the

specified fuses ( Tab. 4-4).

ƒ

Voltage of the fuses must at least be suitable with the input voltage of the

drive.

ƒ

The integral solid state protection does not provide branch circuit protection

and that branch circuit protection has to be provided externally in

accordance with manufacturers instructions, the National Electrical Code

and any additional codes.

ƒ

For information on the protection level of the internal overload protection

for a motor load, see the corresponding Application Manuals or Software

Helps.

ƒ

For information on rating and proper connection of the thermal protector

(only for connection to motors having integral thermal protection), see the

corresponding Application Manuals or Software Helps.

ƒ

Maximum surrounding air temperature: 55 °C with derating.

ƒ

Use 75 °C copper wire only, except for control circuits.

ƒ

Control card protection:
External fuse for 24 Vdc supply voltage of control terminal X2. Rated 4 A DC

fuse UL248-14.

Branch circuit protection (UL Guide No. JHFR2)

Bussmann

Alternate type

Type

Fuse rating

Type

Ferraz-Shawmut

SIBA

E94ASxE1454

250 A, 700 V

170M3016

2061032.250

6.6URD30D08A0250

E94ASxE1724

315 A, 700 V

170M3017

2061032.315

6.6URD30D08A0315

E94ASxE2024

350 A, 700 V

170M3018

2061032.350

6.6URD30D08A0350

E94ASxE2454

400 A, 700 V

170M4012

2061032.400

6.6URD30D08A0400

E94ASxE2924

500 A, 700 V

170M4014

2061032.500

6.6URD30D08A0500

E94ASxE3664

630 A, 700 V

170M4016

206xx32.600

A50-P600

E94ASxE4604

700 A, 700 V

170M4017

2061032.700

6.6URD31D08A0700

E94ASxE5724

900 A, 700 V

170M6013

2063032.900

6.6URD33D08A0900

E94ASxE6354

900 A, 700 V

170M6013

2063032.900

6.6URD33D08A0900

E94ASxE6954

900 A, 700 V

170M6013

2063032.900

6.6URD33D08A0900

Tab. 4-4

ƒ

100 kA SCCR with above fuses.

(Short Circuit Current Rating)

ƒ

Ferraz-Schawmut A50QS fuses may be substituted for A50-P fuses.

ƒ

170M fuses from Bussmann shown use -/80 visual indicator. -TN80 Type T, -/110 or

TN/110 Type T indicater fuses of the same size and amperage may be substituted.