3 operation at rated mains voltage 400 v, Operation at rated mains voltage 400 v, Single-axis controllers – Lenze 9400 Manual User Manual

Page 53: Device size 7

Advertising
background image

Single-axis controllers

Rated data (devices for 400/500V mains)

Operation at rated mains voltage 400 V

4

53

EDS94SPP101 EN 7.1

4.3.3

Operation at rated mains voltage 400 V

Device size 1 ... 6

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

LN

[V]

U

LN

[V]

f [Hz]

3/PE AC

400

320 - 0 % ... 440 + 0 %

45 - 0 % ... 65 + 0 %

2/PE DC

565

455 - 0 % ... 620 + 0 %

-

Mains current at I

aN

Output power

Motor power

(typical)

with external

mains choke

without external

mains choke

U, V, W

4 pol. ASM

Type

I

LN

[A]

I

LN

[A]

S

aN

[kVA]

P

aN

[kW]

P

aN

[hp]

E94ASxE0024

1.5

2.1

0.9

0.37

0.5

E94ASxE0034

2.5

3.5

1.6

0.75

1

E94ASxE0044

3.9

5.5

2.5

1.5

2

E94ASxE0074

7.0

9.9

4.4

3

4

E94ASxE0134

12.0

16.8

8.1

5.5

7.5

E94ASxE0174

15.0

21.0

10.3

7.5

11

E94ASxE0244

20.5

29.0

14.7

11

15

E94ASxE0324

-

29.0

20.0

15

20

E94ASxE0474

-

43.0

29.3

22

29

E94ASxE0594

-

54.0

36.8

30

40

Device size 7

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

LN

[V]

U

LN

[V]

f [Hz]

3/PE AC

400

320 - 0 % ... 440 + 0 %

45 - 0 % ... 65 + 0 %

Mains current at I

aN

Output power

Motor power

(typical)

with external

mains choke

without external

mains choke

U, V, W

4 pol. ASM

Type

I

LN

[A]

I

LN

[A]

S

aN

[kVA]

P

aN

[kW]

P

aN

[hp]

E94ASxE0864

-

79.0

53.6

45

60

E94ASxE1044

-

95.0

64.8

55

73

Advertising