Design of the cables

ƒ

The cables used must comply with the approvals required for the location (e.g. UL).

ƒ

The effectiveness of a shielded cable is reached by:
– Providing a good shield connection through large-surface shield contact.
– Using only braided shields with low shield resistance made of tin-plated or

nickel-plated copper braid.

– Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
– Keeping unshielded cable ends as short as possible.

Use system cables or shielded cables for these connections:

ƒ

Analog signals (inputs and outputs)

ƒ

System bus CAN

ƒ

Resolver

ƒ

Encoder

The following connections need not be shielded:

ƒ

24 V supply

ƒ

Digital signals (inputs and outputs)

Tip!

Parameter setting and configuration can be carried out using the

L-force »Engineer«. For this purpose the Online Help and the Software Manual

for the standard device will guide you.