Power supply modules

Rated data (devices for 400/500V mains)

Fuses and cable cross-sections

6

225

EDS94SPP101 EN 7.1

6.3.4

Fuses and cable cross-sections

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

LN

[V]

U

LN

[V]

f [Hz]

3/PE AC

230 ... 500

180 - 0 % ... 550 + 0 %

45 ... 65

Operation with external mains choke/mains filter
Type

Installation according to EN 60204-1

1)

Installation according

to UL

2)

FI

3)

c

d

L1, L2, L3 - Laying system

e

L1, L2, L3

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[AWG]

[mA]

E94APNE0104

C16

-

2,5

2,5

15

14

300

E94APNE0364

C40

-

10

10

40

8

300

E94APNE1004

-

125

-

50

F: 50

100

1/0

300

E94APNE2454

-

315

-

F: 150

(2 x 70)

250

250 mcm

(2 x 1/0)

300

1)

The details are recommendations. Other designs/laying systems are possible (e.g. according to VDE 0298-4). The

cable cross-sections apply under the following conditions: the use of PVC-insulated copper cables, conductor

temperature < 70°C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.

2)

UL approved cables only, fuses and fuse holders must be used.

UL fuse: voltage 500 ... 600 V

3)

Universal-current sensitive earth-leakage circuit breaker

If several devices or cable lengths > 50 m are used, the circuit breaker may respond, depending on the cable type and

switching frequency.

4)

Device with integrated mains choke

c

Circuit breaker

d

Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category

e

Fuse

Observe national and regional regulations