Accessories (overview), Filters mains filters for single-axis controllers, Rated data – Lenze 9400 Manual User Manual

Page 499

Advertising
background image

Accessories (overview)

Filters

Mains filters for single-axis controllers

9

498

EDS94SPP101 EN 7.1

Rated data

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

LN

[V]

U

LN

[V]

f [Hz]

3/PE AC

230

180 - 0 % ... 264 + 0 %

45 ... 65

3/PE AC

400

320 - 0 % ... 440 + 0 %

45 ... 65

3/PE AC

500

400 - 0 % ... 550 + 0 %

45 ... 65

Voltage

Freq.

Current [A]

Current [A]

Number of

phases

[V]

[Hz]

c

max. +45° C

c

max. +55° C

E94AZMS0034

230/400/500

50/60

3.2/3.2/3.2

2.0/2.0/2.0

3

E94AZMS0094

230/400/500

50/60

9.0/9.0/9.0

5.6/5.6/5.6

3

E94AZMS0184

230/400/500

50/60

18/18/18

11/11/11

3

E94AZMS0314

230/400/500

50/60

31/31/31

19/19/19

3

c

Temperature in the control cabinet

Power loss

Inductance

Voltage drop

P

loss

[W]

L [mH]

Δ

U [V]

E94AZMS0034

15

10

10

E94AZMS0094

23

3.5

10

E94AZMS0184

38

1.1

7.4

E94AZMS0314

48

0.75

7.3