3 overcurrent operation, Overcurrent operation, Multi-axis controllers – Lenze 9400 Manual User Manual

Page 169

Advertising
background image

Multi-axis controllers

Rated data

Overcurrent operation

5

169

EDS94SPP101 EN 7.1

5.3.3

Overcurrent operation

The controllers are designed for two overcurrent modes:

ƒ

5-s-cycle c
– 0.5 s load period with peak current 
– 4.5 s recovery time with limited current 

ƒ

3-min cycle d
– 1 min load period with peak current 
– 2 min recovery time with limited current 

A load period must be followed by a recovery time. During the recovery time the current

must not exceed the value given.
The values given refer to the rated output current I

aN8

.

t

0

100

2

0

1

I

[%]

aN8

3

0.5 s

4.5 s

1 min

2 min



‚

9400SSP008

Fig. 5-1

Overcurrent capacity at 45° C

 Peak current for 0.5 s

c

5-s cycle

 Max. current in the recovery time for 4.5 s

Peak current for 1 min

d

3-min cycle

 Max. current in the recovery time for 2 min