3 overcurrent operation, Overcurrent operation, Multi-axis controllers – Lenze 9400 Manual User Manual
Page 169
Multi-axis controllers
Rated data
Overcurrent operation
5
169
EDS94SPP101 EN 7.1
5.3.3
Overcurrent operation
The controllers are designed for two overcurrent modes:
ƒ
5-s-cycle c
– 0.5 s load period with peak current
– 4.5 s recovery time with limited current
ƒ
3-min cycle d
– 1 min load period with peak current
– 2 min recovery time with limited current
A load period must be followed by a recovery time. During the recovery time the current
must not exceed the value given.
The values given refer to the rated output current I
aN8
.
t
0
100
2
0
1
I
[%]
aN8
3
0.5 s
4.5 s
1 min
2 min
9400SSP008
Fig. 5-1
Overcurrent capacity at 45° C
Peak current for 0.5 s
c
5-s cycle
Max. current in the recovery time for 4.5 s
Peak current for 1 min
d
3-min cycle
Max. current in the recovery time for 2 min