Power supply modules, Arrangement of the devices, Arrange the devices in a row from left to right – Lenze 9400 Manual User Manual

Page 240

Advertising
background image

Power supply modules

Mechanical installation

Devices in the range 100 ... 245 A (48 ... 119 kW)

6

240

EDS94SPP101 EN 7.1

Arrangement of the devices

L1
L2
L3

M

3~

M

3~

M

3~

M

3~

E94AZxPxxxx

E94AZxPxxxx

E94APNExxxx

E94AZEX100

E94AZPxxxxx

E94AZPxxxxx

E94AZPxxxxx

E94AZPxxxxx

...

...

+UG

-UG

+UG

-UG

+UG

-UG

0

1

+

(E94AZPPxxxx)

SSP94FF003

Fig. 6-4

Arrangement concept

Standard mounting: side mounting

Mounting variant: top mounting

E94AZxPxxxx

Filter

E94APNExxxx

9400 DC power supply module
(up to 36 A/18 kW with E94AZPPxxxx installation backplane)

E94AZEX100

DC input module

E94AZPxxxxx

Installation backplane for 9400 axis module

A DC-bus connection has to be planned and dimensioned taking the technical data into

account.
How to arrange the devices via the DC busbars for operation in the DC-bus connection:

ƒ

Arrange the devices in a row from left to right.

ƒ

Install the supplying device on the left:
– DC power supply module (in a first row),
– DC input module (in the following rows).

ƒ

Install the multi drive axis controllers to the right from the highest to the lowest

power (recommendation).

ƒ

For increasing the braking power also single drive axis controllers can be integrated.

For this purpose these axis controllers have to be equipped with the optional busbar

mounting set (E94AZJAxxx).