Single-axis controllers

Wiring

Devices in the range 145 ... 695 A (75 ... 370 kW)

4

124

EDS94SPP101 EN 7.1

Mains

Terminal X100

Marking

Description

L1

L2

L3

Connection of the mains phases L1, L2, L3

SSP94KL0X8

Connection for the PE conductor on the supply side with M8 ring

cable lug

Terminal data

Max. conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Device size 8S:

Flexible

With wire end ferrule

95

000

14

124

Inbus 5

M8 ring cable lug

95

000

9.5

84

WAF 13

Motor temperature monitoring

Terminal X106

Labelling

Description

T1

T2

Motor temperature monitoring with PTC element (type-A sensor,

switching performance according to EN 60947-8 for type-A tripping units)

or thermostat (NC contact).

SSP94X6106

Terminal data

Max. conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

2.5

12

0.5 ... 0.6

4.5 ... 6.2

Slot

0.6 x 3.5

With wire end ferrule