Accessories (overview)

Communication modules

Ethernet interface

9

363

EDS94SPP101 EN 7.1

Connections

Pos.

Description

X245

Connection for the external supply of the communication module

Design: Plug connector with spring connection, 2-pole

X246

EtherCAT input (IN)

Design: RJ45 socket according to IEC 60603-7

X247

EtherCAT output (OUT)

Design: RJ45 socket according to IEC 60603-7

Displays

LED

Description

Pos.

Colour

Condition

MS

green

blinking

The communication module is supplied with voltage but has no

connection to the standard device (standard device is either switched off,

in the initialisation phase, or not available).

on

The communication module is being supplied with voltage and is

connected to the standard device.

ME

red

on

A communication module error has occurred.

BS

green

off

The communication module is in the ”Init” status (initialisation phase).

blinking

(2.5 Hz)

The communication module is in the ”Pre-Operational” status.

blinking

(1.0 Hz)

The communication module is in the ”Safe-Operational” status.

flickering

The communication module is booting and has not yet reached the ”Init”

status (initialisation phase).

on

The communication module is in the ”Operational” status.

BE

red

blinking

Bus error/trouble is active (e.g. the Ethernet cable is unplugged). The LED

is blinking in parallel to the BS LED.

DE

red

on

The communication module is not accepted by the standard device or

the standard device is not active. (See notes provided in the

documentation for the standard device.)

Signalling at connection X246/X247:
-

Red

On / blinking The EtherCAT connection is disrupted or not available.

-

Green

On / blinking

z

The EtherCAT connection is available.

z

The data communication of the EtherCAT connection is active.