Power supply modules

Rated data (devices for 400/500V mains)

Operation at rated mains voltage 400 V

6

222

EDS94SPP101 EN 7.1

Output current and output power

100 %

5-s cycle

3-min cycle

Type

I

DC

[A]

P

DC

[kW]

I

DC

[A]

P

DC

[kW]

I

DC

[A]

P

DC

[kW]

E94APNE0104

10

3.6

40

14.4

15

5.4

E94APNE0104

+ E94AZMP0084

10

4.9

40

19.6

15

7.4

E94APNE0364

36

13.0

108

39.0

54

19.5

E94APNE0364

+ E94AZMP0294

36

17.5

108

52.5

54

26.3

E94APNE1004

100

36.2

200

109

150

54.3

E94APNE1004

+ E94AZMP0824

100

48.6

200

146

150

72.9

E94APNE2454

245

88.6

368

266

368

133

E94APNE2454

+ E94AZMP2004

245

119

368

357

368

179

100 %

Permanent rated values

5-s cycle

Cycle for the second-range
(0.5 s overload/4.5 s recovery time with 75 % of the permanent rated value)

3-min cycle

Cycle for the minute-range
(60 s overload/120 s recovery time with 75 % of the permanent rated value)

Internal brake chopper data

R

Bmin

[Ω]

I

BRmax

[A]

P

BRmax

[kW]

I

BRd

[A]

P

Bd

[kW]

t

Z

[s]

t

on

[s]

t

fp

[s]

Type
E94APNE0104

27.0

26.9

19.5

9.7

2.6

4.3

0.5

0.5

E94APNE0364

12.0

60.4

43.8

27.0

8.7

3.0

0.5

0.5

E94APNE1004

5.0

145

105

58.2

17.0

3.6

0.5

0.5

E94APNE2454

2.8

259

188

104

30.3

3.6

0.5

0.5

R

Bmin

Minimum brake resistance, nominal value ±10 %

I

BRmax

Peak current

P

BRmax

Peak braking power

I

BRd

Continuous current RMS - important for the dimensioning of the cables

P

Bd

Continuous braking power

t

Z

Cycle time, periodic load change with running time and recovery time

t

on

Running time

t

Z

- t

on

Recovery time

t

fp

Maximum running time without initial load and compliance with the recovery

time