Safety instructions – Lenze 9400 Manual User Manual

Page 33

Advertising
background image

Safety instructions

General safety and application instructions for Lenze motors

3

33

EDS94SPP101 EN 7.1

Installation
Ensure an even surface, solid foot and flange mounting and exact alignment if a direct

clutch is connected. Avoid resonances with the rotational frequency and double mains

frequency which may be caused by the assembly. Turn rotor by hand, listen for unusual

slipping noises. Check the direction of rotation when the clutch is not active (observe

section ”Electrical connection”).
Use appropriate means to mount or remove belt pulleys and clutches (heating) and cover

them with a touch guard. Avoid impermissible belt tensions.
The machines are half-key balanced. The clutch must be half-key balanced, too. The visible

jutting out part of the key must be removed.
If required, provide pipe connections. Designs with shaft end at bottom must be protected

with a cover which prevents the ingress of foreign particles into the fan. Free circulation of

the cooling air must be ensured. The exhaust air - also the exhaust air of other machines

next to the drive system - must not be taken in immediately.

Electrical connection
All operations must only be carried out by qualified and skilled personnel on the

low-voltage machine at standstill and deenergised and provided with a safe guard to

prevent an unintentional restart.This also applies to auxiliary circuits (e. g. brake, encoder,

blower).
Check safe isolation from supply!
If the tolerances specified in EN 60034-1; IEC 34 (VDE 0530-1) - voltage ±5 %, frequency

±2 %, waveform, symmetry - are exceeded, more heat will be generated and the

electromagnetic compatibility will be affected.
Observe the data on the nameplate, operating notes, and the connection diagram in the

terminal box.
The connection must ensure a continuous and safe electrical supply (no loose wire ends);

use appropriate cable terminals. The connection to the PE conductor must be safe. The

plug-in connector must be bolt tightly (to stop).
The clearances between blank, live parts and to earth must not fall below 8 mm at

U

r

550 V, 10 mm at U

r

725 V, 14 mm at U

r

1000 V.

The terminal box must be free of foreign particles, dirt and moisture. All unused cable

entries and the box itself must be sealed against dust and water.

Advertising