Accessories (overview) – Lenze 9400 Manual User Manual
Page 367
Accessories (overview)
Communication modules
Ethernet interface
9
367
EDS94SPP101 EN 7.1
Connections
Pos.
Connection
Description
A1,
A2 ... A8
Ethernet
RJ45 socket to EN 50173
B
DC voltage supply
Plug connector with spring connection, 4-pole
PE
M3 thread
Use the uplink port A1 to cascade the hubs:
E94AZCEH003
The hubs can be connected using a patch or a crossover cable.
Use the MDI / MDIX switch to select the uplink mode as shown in the following figure:
Patch cable
Crossover cable
E94YCEH005
Switch
Pos.
Element
Explanation
C
Pushbutton switch
Activates Rx/Tx crossing for connection A1:
z
ON: MDIX
z
OFF: MDI
Displays
LED
Description
Pos.
Colour
Condition
OK
Yellow
On
Device is supplied with voltage.
Rx1
...
Rx8
Yellow
On
Activity
Connections A1 ... A8 send or receive data.
Blinking
L/C1
...
L/C8
Green
On
Link
Connections A1 ... A8 are connected to the Ethernet network.
Red
On
Collision
Connection between connections A1 ... A8 and the Ethernet network is
inhibited due to collision.