Accessories (overview), Danger, Warnings – Lenze 9400 Manual User Manual

Page 483

Advertising
background image

Accessories (overview)

Components for operation in the DC-bus connection

DC-feeding point

9

483

EDS94SPP101 EN 7.1

Rated data

Basis of the data
Mains

Voltage

U

DC

[V]

Voltage range

U

DC

[V]

Frequency range

f [Hz]

2/PE DC

325

260 - 0 % ... 370 + 0 %

-

2/PE DC

565

455 - 0 % ... 620 + 0 %

-

2/PE DC

705

565 - 0 % ... 775 + 0 %

-

Voltage

Frequency

Current [A]

Number of

phases

[V]

[Hz]

max. +45 °C c

max. +55 °C c

E94AZEX100

325/565/705

0 (DC)

100/100/100

75/75/75

2

c

Temperature in the control cabinet

Safety instructions

Danger!

Hazardous electrical voltage
During operation and up to 3 minutes after power-off, hazardous electrical

voltages may occur at the DC input module connections.
Possible consequences:

ƒ

Death or serious injuries when touching the connections.

Protective measures:

ƒ

Disconnect all devices in the DC-bus connection from the mains before

working on the input module.

ƒ

Check if no voltage is applied to the power terminals.

Warnings!

ƒ

Maximum surrounding air temperature: 55 °C

ƒ

Use 60/70 °C copper wires only.

ƒ

Use appropriate listed (ZMVV) wire connectors and soldering lugs, suitable

for current and voltage.

Note!

The place of installation and mounting material must ensure a permanent

mechanical connection.
We recommend to keep to the hole patterns of the axis modules when fixing

the DC input module. The hole spacing corresponds to device size I. For further

information, please see the Mounting Instructions for the axis module

installation backplane (EDK94ZPM113).