Multi-axis controllers

General data and operating conditions

5

162

EDS94SPP101 EN 7.1

The available protective insulation within the controller of the ” 9400 Servo Drives” series

in accordance with EN 61800-5-1 is implemented with a rated voltage for the external

conductor/star point of up to 300 V for mains with neutral earthing.
The following graphic representation

ƒ

shows the arrangement of the terminal strips and the separate potential areas of

the controller.

ƒ

serves to determine the relevant protective insulation between two terminals in

differently insulated separate potential areas.

Reinforced insulation

Basic insulation

Functional insulation

Protective insulation acc. to

EN 61800-5-1

(Definition of terms: see glossary)

Ext. DC

I/O

X4

X6

X6

X5

X7

X7

X8

X8

X3

X2

X1

X105

X105

X106

X100

X107

MXI1

MXI2

Bus

Ext. DC

MSI

MMI

E94YCXX007zl

Terminal strip

Terminal

Terminal strip

Terminal

X100

z

L1, L2, L3

(only single drive)

z

+UG, -UG

X1

CAN on board 9400

X2

z

State bus

z

24 V (ext.)

X105

z

U, V, W

z

Rb1, Rb2

(only single drive)

X3

Analog input/output

X106

Motor PTC

X4

Digital outputs

X107

Control of motor holding

brake

X5

Digital inputs

X6

Diagnostics

X7

Resolver

X8

Encoder

MXI1, MXI2

Extension module

MMI

Memory module

MSI

Safety module

Example
Which type of protective insulation is used between the bus terminal of the device module

in slot MXI1 or MXI2 and the mains terminal X100?
The separate potential area with the better protective insulation is decisive.

ƒ

The separate potential area of the device module bus terminal is ”functionally

insulated”.

ƒ

The separate potential area of the mains terminal has a ”reinforced insulation”.

Result: The insulation between the mains terminal X100 and the bus terminal is of the

”reinforced insulation” type.