Power supply modules

Rated data (devices for 400/500V mains)

Mains filters for power supply modules

6

228

EDS94SPP101 EN 7.1

With different motor cable lengths, per axis at least 25 % of the longest cable must be

considered when calculating the total motor cable length.

Example: 1

Motor cable length l

mot

[m]

Axis

Actual

value

min. 25 % of the longest cable

To be considered

1

6

0.25 * 20 = 5

6

2 ... 4

3 * 10

3 * 10

5

20

Õ

20

Total

56

max. permissible for 5 axes: ∑< 60

56

EMC class C2 will be complied with.

;

Example: 2

Motor cable length l

mot

[m]

Axis

Actual

value

min. 25 % of the longest cable

To be considered

1 ... 4

4 * 5

0.25 * 40 = 10

4 * 10

5

40

Õ

20

Total

60

max. permissible for 5 axes: ∑< 60

80

EMC class C2 will not be complied with.

:

Other interference factors
Compliance of EMC class C2 may also be interfered with by other factors:

ƒ

Distribution of axis modules over several control cabinets

ƒ

No use of Lenze system cables or cables with the same specifications

ƒ

Poor connection of motor cable shields

ƒ

Motor cable interruptions

ƒ

Other interference sources (e.g. switched-mode power supplies)

ƒ

Synchronous switching of limit switches