Accessories (overview) – Lenze 9400 Manual User Manual

Page 381

Advertising
background image

Accessories (overview)

Communication modules

PROFIBUS

9

381

EDS94SPP101 EN 7.1

Specification of the transmission cable
Please follow the specifications of the PROFIBUS user organisation (PNO) for signal cables:

Area

Values

Specific resistance

135 ... 165 Ω/km, (f = 3 ... 20 MHz)

Capacitance per unit length

30 nF/km

Loop resistance

< 110 Ω/km

Core diameter

> 0.64 mm

Core cross-section

> 0.34 mm

2

Cores

Double twisted, insulated and shielded

Baud rate / length of bus cable

Baud rate [kbps]

Length [m]

9.6 ... 93.75

1200

187.5

1000

500

400

1500

200

3000 ... 12000

100

Tip!

For high baud rates we recommend to consider the application of optical

fibres.
Advantages of optical fibres:

ƒ

Electromagnetic interferences on the transmission path remain ineffective.

ƒ

Bus lengths of several kilometres are also possible with higher baud rates.

The bus length is

– independent of the baud rate.

– dependent on the optical fibre used.