Single-axis controllers – Lenze 9400 Manual User Manual

Page 128

Advertising
background image

Single-axis controllers

Wiring

Devices in the range 145 ... 695 A (75 ... 370 kW)

4

128

EDS94SPP101 EN 7.1

DC bus

Terminal X100

Marking

Description

Connection with ring

cable lug for M8

+UG

-UG

Alternative option for DC-bus voltage connection (compatible to

9300 series).

SSP94KL801

Terminal data

Max. conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Device size 8:

E94ASxE1724

E94ASxE2024

2 x 240

2 x 500 mcm

9.5

84

WAF 13

Device size 9:

E94ASxE2454

E94ASxE2924

E94ASxE3664

Tip!

Now mount the barrier between mains input and power terminals, if had been

removed to have more free space for wiring.

Operation with DC supply
ForoperationwithDCsupply, theinternal fansmust beconnected viathe internalterminal

FK103 to the 400/500 V AC mains voltage.
When opening the upper housing cover, you will find the pluggable terminal FK103 at the

top in the device on the switched-mode power supply card.

94SSPGG852

Interface card

Switched-mode power supply card

FK103

Fan voltage terminal

Remove the cable bridges of the terminal. Then, connect the mains voltage to

FK103.101/100.

Advertising