3 earthing of internal emc filters, Earthing of internal emc filters, Regenerative power supply modules – Lenze 9400 Manual User Manual

Page 294

Advertising
background image

Regenerative power supply modules

Wiring

Earthing of internal EMC filters

7

294

EDS94SPP101-7.1

7.6.3

Earthing of internal EMC filters

Device-internal EMC filters have been implemented to reduce interference emission.

These EMC filters are connected to protective earth to discharge interference currents.
Under certain conditions the EMC filters must be disconnected from:

ƒ

Operation in an IT system
The devices are protected from damages or destruction due to incompatible

overvoltages in the case of an error (earth fault).

ƒ

DC-bus operation

ƒ

Operation with power supply modules or regenerative power supply modules

ƒ

Operating multiple devices with a common filter
The EMC properties can only be reached by carrying out the described measures.
The triggering behaviour of applicable earth-leakage circuit breakers remains

undisturbed.

Overview of the measures
The measures can be carried out easily. They are prepared device-dependently, and their

mounting and wiring are described.

Device

Measure

Controller

With installation backplane (GG1 ... GG3)

Plug/unplug the plastic cap

Without installation backplane (GG6 ... GG7)

Change the screwed connection

Without installation backplane (GG8S ... GG10)

Activate the switch

Power supply modules

With installation backplane (GG1 und GG3)

Plug/unplug the plastic cap

Without installation backplane (GG4 ... GG5)

---

Regenerative power supply module

With installation backplane (GG3)

Plug/unplug the plastic cap

Suitable mains filter

Change the screwed connection

Advertising