Multi-axis controllers

Control terminals

5

212

EDS94SPP101 EN 7.1

Setting the supply voltage
The supply voltage of the encoder must be adapted to the cable length.
For this purpose, use the ”Encoder voltage” parameter, C00421.

Encoder

U

r

Voltage setting [V] in C00421 for cable length [m]

Product key

[V]

0 - 10

10 - 30

30 - 50

50 - 70

70 - 90

90 - 100

100 -150

TTL

IG2048-5V-T

5 ±5%

5.0

5.0

5.1

5.1

5.2

5.2

5.3

IG4096-5V-T
IK2048-5V-T
IK4096-5V-T

Sin/cos

IG1024-5V-V

5 ±5%

5.0

5.0

5.1

5.1

5.2

5.2

5.3

IG2048-5V-S

Sin/cos (Hiperface)

AS1024-8V-H

8

(7 ... 12)

8.0

AM1024-8V-H

Sin/cos (Endat)

AM32-5V-E

5 ±5%

5.0

AS2048-5V-E
AM2048-5V-E

Tab. 5-2

U

r

Rated encoder voltage

The values listed in Tab. 5-2 are valid for the use of Lenze system cables at typical ambient

temperatures.
Other cables, other cable cross-sections, or extreme ambient temperatures may require

adaptations determined by means of measurements.
For a higher encoder supply power, e.g. for laser-based length measuring systems, an

external encoder supply must be provided.