Wiring

Devices in the range 2 ... 24 A (0.37 ... 11 kW)

4

112

EDS94SPP101 EN 7.1

How to proceed:
1. Strip the motor cable  according to dimensions given.
2. Fold back the shield of the motor cable  over the cable sheath.
3. Stabilise the shield with self-adhesive conductive foil  (recommendation).
4. Fix the shield and conductive foil with heat-shrinkable tube  on the cable sheath.
5. Fasten cable lugs or wire end ferrules.
6. Connect the shields separately to the shield sheet using shield clamps (no strain

relief).

E94AZJS-013