Power supply modules

Final works

6

260

EDS94SPP101 EN 7.1

6.8

Final works

Danger!

Dangerous voltage!
Depending on the device, the DC-bus voltage is still charged for

approx. 3 ... 20 min after switching off the mains voltage.

ƒ

The state of charge is not indicated!

ƒ

On synchronous motors self-discharge only starts after a possible feedback

operation has been completed.

ƒ

Discharging the DC bus in a controlled manner via the brake chopper/brake

resistor requires the external 24 V supply ( digital input DI1).

Possible consequences:

ƒ

Death or severe injuries when touching the terminals.

Protective measures:

ƒ

Before starting work on the system check that it is deenergised.

ƒ

Wait at least 3 minutes after switching off the mains voltage.

ƒ

Only remove deenergised standard devices from the installation backplanes

and do not touch any terminals.

How to proceed:

ƒ

Adjust the setting for the mains voltage/brake chopper threshold to the mains

Setting of mains voltage/brake chopper threshold

2

Pos.

U

LN

[V]

U

BRmax

[V]

1

500 V
480 V
400 V
230 V

ON

MAINS

12

500

790

OFF

OFF

480

765

ON

OFF

400

725

OFF

ON

230

390

ON

ON

94APNEDS01

ƒ

Switch on the 24 V supply

ƒ

Check the operating status by means of the LED display

If you want to continue commissioning:

ƒ

Switch on the mains