Power supply modules – Lenze 9400 Manual User Manual

Page 259

Advertising
background image

Power supply modules

Control terminals

6

259

EDS94SPP101 EN 7.1

Digital inputs, digital outputs

Terminal X12

Labelling

Description

GOI

GND digital out/in

DI1

External control of the brake chopper; its only purpose is to

synchronise the brake choppers if a second power supply module is

used.

DO1

Mains OK

DO2

Brake chopper active

DO3

Short circuit in brake chopper

SSP9400X12

DO4

Heatsink overtemperature

Terminal data

Conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

0.2 ... 2.5

24 ... 12

Spring terminal

With wire end

ferrule

Stripping length / contact length: 10 mm

Synchronisation
The device-internal brake chopper operates automatically and independently even if the

control inputs are not wired.
Depending on the selected mains voltage, the brake resistor is connected if the DC-bus

voltage is exceeded (e.g. due to excessive braking energy).
If the brake choppers of power supply modules in a DC-bus connection need to be

synchronised, proceed as follows:
1. The 24-V supply of the control card (X11) must be independent of the mains voltage

at the mains connection and switched on.

2. All power supply modules of the DC-bus connection must have the same brake

chopper threshold (according to the mains).

3. The DO2 (X12) digital output of the master power supply module needs to be wired

to the DI1 (X12) digital input of every other power supply module of the DC-bus

connection. The GOI connections (X12) of all power supply modules of the DC-bus

connection must be interconnected.