Multi-axis controllers

Wiring

Devices in the range 2 ... 32 A (0.37 ... 15 kW)

5

191

EDS94SPP101 EN 7.1

E94AZJA-008

Fig. 5-10

Example: connecting busbars to DC power supply module

Proceed as follows to connect the busbars:
1. If devices of the interconnected system have already been in operation:

– Ensure that the power supply system is switched off by checking the voltage at the

supply terminals.

– If necessary, switch off the power supply and wait at least 3 minutes.

2. Loosen the busbar screws but do not remove them completely.
3. Push the busbars as far as possible to the left towards the adjacent busbar.

– Ensure that there is good contact to the adjacent busbar.

4. Tighten the busbar screws.

– Tightening torque: 3.2 ... 3.5 Nm (28 ... 31 lb-in).

5. Screw all components onto the mounting plate.

– Tightening torque: 3.4 Nm (30 lb-in).