Accessories (overview), Rated data – Lenze 9400 Manual User Manual
Page 515
Advertising
Accessories (overview)
Filters
Mains filters for regenerative power supply modules
9
514
EDS94SPP101 EN 7.1
Rated data
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
LN
[V]
U
LN
[V]
f [Hz]
3/PE AC
230
180 - 0 % ... 264 + 0 %
45 ... 65
3/PE AC
400
320 - 0 % ... 440 + 0 %
45 ... 65
3/PE AC
500
400 - 0 % ... 550 + 0 %
45 ... 65
Voltage
Freq.
Current [A]
Current [A]
Number of
phases
[V]
[Hz]
c
max. +45° C
c
max. +55° C
E94AZMR0264xDB
230/400/500
50/60
26/26/26
19/19/19
3
E94AZMR0474xDB
230/400/500
50/60
47/47/47
35/35/35
3
c
Temperature in the control cabinet
Power loss
Inductance
Regenerative
inductance
Voltage drop
P
V
[W]
L [mH]
L
gen
[mH]
Δ
U [V]
E94AZMR0264SDB
65
0.77 ±10 %
0.84 ±10 %
6.3
E94AZMR0264LDB
72
E94AZMR0474SDB
85
0.42 ±10 %
1.54 ±10 %
6.2
E94AZMR0474LDB
101
Advertising