Example 1 - supply module with multi-axis controllers

Assumptions:

ƒ

400 V, 3 AC/PE

ƒ

7 axes in 2 power categories

ƒ

no particular dynamic performance requirements

The following motors (Mx) are selected:

Motor type

Rated power

Efficiency

Rated current

Index

[kW]

[A]

M1 ... M5

MCS14H15

2.5

0.92

6.6

M6 ... M7

MCS09F38

1.2

0.90

2.5

For the above motor data, the following controllers (Gx) are selected:

Controller

Rated power

Typical motor

power

Power loss P

l

Rated current

Index

[kW]

[kW]

[kW]

[A]

G1 ... G5

E94AMxE0074

4.8

3.0

0.19

7.0

G6 ... G7

E94AMxE0034

1.7

0.75

0.12

2.5

The power required by the drive system is determined with the below formula ( 8.5.5):
P

DCtotal

= 5 * (2.5 kW / 0.92 + 0.19 kW) + 2 * (1.2 kW / 0.90 + 0.12 kW)

P

DCtotal

= 17.4 kW

The calculated power requirement is used to select the supply module:

Supply module (+ mains filter)

Rated power (P

DC100%

)

Index

[kW]

V1

E94APNE0364

+ E94AZMP0294

17.5

Note: Only the supply module with mains filter reaches the required power.

Checking the power efficiency:
With 17.5 kW > 17.4 kW, P

DC100%

> P

DCtotal

.

Select cables and fuses in accordance with the Technical data.

L2

L1

L3

M

M

M

3

AC

M

...

V1

G 1

G x

Fig. 8-4

Basic circuit diagram