Multi-axis controllers, Control terminals, Supply to the sine and cosine track – Lenze 9400 Manual User Manual

Page 209

Advertising
background image

Multi-axis controllers

Control terminals

5

209

EDS94SPP101 EN 7.1

Resolver
Resolvers are connected to X7 (9-pole Sub-D socket).
The use of third-party resolvers is permissible. For this purpose the number of pole pairs of

the resolver in C00080 must be adapted to the resolver used. When the stator coils are

excited with 4 kHz, the apparent impedance of the connected resolver must not fall below

65 Ohm. When lower impedances are connected, the overload protection integrated in the

resolver output limits the output current and can falsify the resolver evaluation.
Resolvers are operated in reverse mode:

ƒ

Supply to the sine and cosine track,

ƒ

Both signals are controlled in a way that the current flow on the reference track is

reduced to zero.

Electrical data
General

Cable length (system cable recommended)

Max. 150 m

V

CC

Supply voltage

5 V

Maximum output current

110 mA

+REF, -REF

Input frequency

Max. 250 kHz

+COS, -COS

+SIN, -SIN

Excitation voltage

10 V

SS

Carrier frequency

4 kHz, fix

+KTY, -KTY

Type

KTY 83-110

+REF

-REF

+COS

+SIN

-SIN

-COS

+KTY

-KTY

1

2

3

4

5

6

7

8

9

X7

KTY

V

CC

ETS

SSP94RESX7

Fig. 5-18

Wiring principle

Terminal X7

Labelling

Description

1

+REF

2

-REF

3

V

CC

4

+COS

5

-COS

6

+SIN

7

-SIN

8

+KTY

9400SSP000X7

9

-KTY