Single-axis controllers – Lenze 9400 Manual User Manual

Page 67

Advertising
background image

Single-axis controllers

Rated data (devices for 400/500V mains)

Fuses and cable cross-sections

4

67

EDS94SPP101 EN 7.1

Operation without external mains choke/mains filter
Type

Installation according to EN 60204-1

1)

Installation according

to UL

2)

FI

3)

c

d

L1, L2, L3 - Laying system

e

L1, L2, L3

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[AWG]

[mA]

E94ASxE0024

C10

-

1,5

1,5

-

10

18

300

E94ASxE0034

C10

-

1.5

1.5

-

10

18

300

E94ASxE0044

C10

-

1.5

1.5

-

10

18

300

E94ASxE0074

C16

-

2.5

2.5

-

15

16

300

E94ASxE0134

C20

-

2.5

2.5

-

20

12

300

E94ASxE0174

C25

-

4

4

-

25

10

300

E94ASxE0244

C40

-

10

6

-

40

8

300

E94ASxE0324

4)

-

40

10

6

-

40

8

300

E94ASxE0474

4)

-

63

16

10

-

60

4

300

E94ASxE0594

4)

-

80

25

25

-

80

2

300

E94ASxE0864

4)

-

100

50

35

-

100

1

300

E94ASxE1044

4)

-

125

70

50

-

125

0

300

E94ASxE1454

4)

-

200

-

-

70

250

000

300

E94ASxE1724

4)

-

250

-

-

95

300

350 mcm

300

E94ASxE2024

4)

-

315

-

-

150

350

500 mcm

300

E94ASxE2454

4)

-

350

-

-

150

2 x 200

0000

300

E94ASxE2924

4)

-

400

-

-

185

2 x 250

2 x 250 mcm

300

E94ASxE3664

4)

-

500

-

-

240

2 x 300

2 x 350 mcm

300

E94ASxE4604

4)

-

2 x 350

-

-

150

2 x 350

500 mcm

300

E94ASxE5724

4)

-

2 x 400

-

-

185

2 x 400

600 mcm

300

E94ASxE6354

4)

-

2 x 450

-

-

240

2 x 400

600 mcm

300

E94ASxE6954

4)

-

2 x 500

-

-

240

2 x 400

600 mcm

300

1)

The details are recommendations. Other designs/laying systems are possible (e.g. according to VDE 0298-4). The

cable cross-sections apply under the following conditions: the use of PVC-insulated copper cables, conductor

temperature < 70°C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.

2)

UL approved cables only, fuses and fuse holders must be used.

UL fuse: voltage 500 ... 600 V

3)

Universal-current sensitive earth-leakage circuit breaker

If several devices or cable lengths > 50 m are used, the circuit breaker may respond, depending on the cable type and

switching frequency.

4)

Device with integrated mains choke

c

Circuit breaker

d

Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category

e

Fuse

Observe national and regional regulations