Regenerative power supply modules

Wiring

Design of the cables

7

297

EDS94SPP101-7.1

7.6.5

Design of the cables

ƒ

The cables used must comply with the approvals required for the location (e.g. UL).

ƒ

It is imperative to comply with the regulations concerning minimum cross-sections

of PE conductors. The cross-section of the PE conductor must be at least as large as

the cross-section of the power connections.

ƒ

The effectiveness of a shielded cable is reached by:
– Providing a good shield connection through large-surface shield contact.
– Using only braided shields with low shield resistance made of tin-plated or

nickel-plated copper braid.

– Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
– Keeping unshielded cable ends as short as possible.

Use system cables or shielded cables for these connections:

ƒ

External brake resistor ( Mounting Instructions of the brake resistor)

ƒ

Analog signals (inputs and outputs)

ƒ

CAN system bus

ƒ

Resolver

ƒ

System connection for synchronisation

The following connections need not be shielded:

ƒ

Mains

ƒ

DC bus

ƒ

24 V supply

ƒ

Digital signals (inputs and outputs)

7.6.6

How to connect the shield