Single-axis controllers

Rated data (devices for 400/500V mains)

Operation at rated mains voltage 230 V

4

52

EDS94SPP101 EN 7.1

Rated data for internal brake chopper

R

Bmin

[Ω]

I

BRmax

[A]

P

BRmax

[kW]

I

BRd

[A]

P

Bd

[kW]

t

Z

[s]

t

on

[s]

t

fp

[s]

Type
E94ASxE0024

47

8.3

3.2

3.7

0.64

5

0.7

1.1

E94ASxE0034

47

8.3

3.2

3.7

0.64

5

0.7

1.1

E94ASxE0044

27

14.4

5.6

5.9

0.95

5

0.6

1.0

E94ASxE0074

27

14.4

5.6

6.9

1.3

5

0.8

1.0

E94ASxE0134

18

21.7

8.5

10.6

2.0

5

0.8

1.2

E94ASxE0174

9

43.3

16.9

20.3

3.7

5

0.7

1.1

E94ASxE0244

9

43.3

16.9

24.5

5.4

5

1.1

1.6

E94ASxE0324

9

43.3

16.9

28.5

7.3

600

260

600

E94ASxE0474

7.5

52.0

20.3

37.9

10.8

600

320

600

E94ASxE0594

7.5

52.0

20.3

44.2

14.7

600

430

600

E94ASxE0864

3.8

102.6

40.0

75.5

21.6

600

320

600

E94ASxE1044

3.8

102.6

40.0

83.5

26.4

600

400

600

R

Bmin

Minimum brake resistance, nominal value ±10 %

I

BRmax

Peak current

P

BRmax

Peak braking power

I

BRd

Continuous current RMS - important for the dimensioning of the cables

P

Bd

Continuous braking power

t

Z

Cycle time, periodic load change with running time and recovery time

t

on

Running time

t

Z

- t

on

Recovery time

t

fp

Maximum running time without initial load and compliance with the recovery

time

Note on the brake chopper data
The brake chopper can output the peak braking power maximally for the specified time t

on

within a cycle time t

Z

.

The brake chopper can output the peak braking power from unloaded states once for the

time t

fp

, e. g. after mains connection or after a recovery time of > 5 x t

Z

.

If the times are exceeded, the brake chopper is clocked so that only the continuous braking

power is output. This serves to the protection of the brake chopper, however, it does not

protect the brake resistor. The brake resistor connected can be protected separately by

parameterisation (C00129 ... C00133) or a thermal contact.
Further information can be found in the software manual.