Single-axis controllers

Control terminals

4

148

EDS94SPP101 EN 7.1

Digital inputs
The controller is provided with freely configurable digital inputs which can be used for

touch probe measurement (edge-controlled event).
The control input RFR for controller enable is firmly connected with the device control. It

must be wired to enable the controller with a HIGH signal.

Electrical data
24O

(external voltage source,

optional)

Rated voltage

24 V

According to IEC 61131-2

Current consumption

Max. 50 mA

RFR

DI1

...

DI8

Switching level

According to IEC 61131-2

LOW

0 V ... +5 V

HIGH

+15 V ... +30 V

Input current

Max. 8 mA

Note!

Digital inputs and digital outputs have separated reference potentials (GI and

GO). If you interconnect inputs and outputs, the reference potentials are

connected as well by an external bridge.

GND

Out

0

1

DI8

DI...

DI2

DI1

RFR

GI

X5

DI8

DI...

DI2

DI1

RFR

GI

X5

DO4

DO3

DO2

DO1

24O

GO

X4

SSP94X5DI1

Fig. 4-33

Wiring principle

Wiring of an external digital signal, e.g. a PLC

Wiring with a slave drive

X4

Terminal for the digital outputs

X5

Terminal for the digital inputs

Out

digital output signal, e.g. of a control

GND

Earth reference potential