Accessories (overview)

Safety modules

SM301

9

415

EDS94SPP101 EN 7.1

Addressing
ThesafetyaddressservestoclearlyassignthesafetymodulesoftheSM301typeinsystems

with several drives. The address ”0” is not permissible.

Address switch
The safety address can be set in the left part of the housing by means of the DIP switch .

For setting the switch, use an appropriately small tool, e. g. a probe. The switch can only be

set if the module is not connected to a standard device. Via the switch, addresses in the

range of 0 ... 1023 can be set. Alterations by the switch with regard to the address are only

activated when the 24-V supply is switched on. The address setting ”0” requires the setting

by the address code.

DIP switch

Labelling

1

2

3

4

5

6

7

8

9

0

Value of the address bit

1

2

4

8

16

32

64

128

256

512

Note!

In the SM301 safety module as of version VA 1.xx, the address 0 is replaced as

follows:

ƒ

With the address saved in the safety module in the parameter

”Safety address” (C15111).

ƒ

If the address 0 canot be replaced, the module reports an error.