Single-axis controllers

Wiring

Earthing of internal EMC filters

4

106

EDS94SPP101 EN 7.1

Device size 8S ... 10
How to separate the internal connection of filters to the protective earth:
1. Remove the upper housing cover.
2. The S300 switch can be found on the Interface card. The Interface card is located in

the top of the device.
– ON position: Standard operation at earthed-neutral systems (Lenze).
– OFF position: Operation at IT systems.

3. Push the S300 switch into the OFF position.

94ITSW8001

ON - Standard

OFF - IT

IF-Card-SW

IF-Card-SW