Single-axis controllers – Lenze 9400 Manual User Manual
Page 136
Single-axis controllers
Wiring
Devices in the range 145 ... 695 A (75 ... 370 kW)
4
136
EDS94SPP101 EN 7.1
Mains
Terminal X100
Marking
Description
Connection with ring
cable lug for M10
L1
L2
L3
Connection of the mains phases
SSP94KL801
Connection for the PE conductor on the supply side
Terminal data
Max. conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Device size 10:
E94ASxE4604
E94ASxE5724
E94ASxE6354
E94ASxE6954
2 x 400
3 x 150
2 x 750 mcm
3 x 350 mcm
19
168
WAF 16
Motor temperature monitoring
Terminal X106
Labelling
Description
T1
T2
Motor temperature monitoring with PTC element (type-A sensor,
switching performance according to EN 60947-8 for type-A tripping units)
or thermostat (NC contact).
SSP94X6106
Terminal data
Max. conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
2.5
12
0.5 ... 0.6
4.5 ... 6.2
Slot
0.6 x 3.5
With wire end ferrule