Regenerative power supply modules

Rated data (devices for 400/500V mains)

Mains filters for regenerative power supply modules

7

279

EDS94SPP101-7.1

7.3.7

Mains filters for regenerative power supply modules

When using the mains filters assigned, conditions must be observed for compliance with

EMC class C2:

ƒ

The measures for the use on IT systems must be applied to all axis modules in the

interconnection (separation of internal filter components from PE, ( 331)).

ƒ

The maximum sum total of all motor cable lengths (Σ l

mot

) for the filter used must

be observed.

Motor cable lengths in the interconnection
The assigned filters are designed for Σ l

mot

(E94AZMR...SDB: 60 m (= 6 x 10 m), E94AZMR...LDB: 500 m (= 10 x 50 m)).
For a different number of axis modules, Σ l

mot

can be determined from the following

diagrams.

25

30

35

40

45

50

55

60

65

70

2

4

6

8

10

12

14

16

18

20

Σl

[m]

n

SSP94FF015 B

Fig. 7-5

Filter E94AZMR...SDB (short distance): Sum total of motor cable lengths as a function of the number

of axis modules

6

8

10

12

14

16

18

20

n

250

300

350

400

450

500

550

600

650

700

Σl

[m]

SSP94FF015 A

Fig. 7-6

Filter E94AZMR...LDB (long distance): Sum total of motor cable lengths as a function of the number

of axis modules