Accessories (overview) – Lenze 9400 Manual User Manual

Page 526

Advertising
background image

Accessories (overview)

Filters

RFI filters for single-axis controllers

9

525

EDS94SPP101 EN 7.1

Mains

Terminal X301

Labelling

Description

L1

L2

L3

Connection of the mains phases L1, L2, L3

Connection for the supply-side PE conductor with ring cable lug M8

SSP94FF606

Terminal data

Max. conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

E94AZxS0544

50

0

10

88.5

Hexagon

socket 5

E94AZxS0954

95

000

14

124.0

PE connection data

Starting torque

[mm]

[Nm]

[lb-in]

E94AZxS0544

M8

12

106

SW 13

E94AZxS0954

Standard device

Cable X302

Labelling

Description

1

2

3

Filter output conductor (lead with wire end ferrules, colour BK)

PE

Output-side PE conductor (lead with wire end ferrule, colour GN/YE)

SSP94FF607