Accessories (overview)

Filters

Mains filters for power supply modules

9

504

EDS94SPP101 EN 7.1

Rated data

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

LN

[V]

U

LN

[V]

f [Hz]

3/PE AC

230

180 - 0 % ... 264 + 0 %

45 ... 65

3/PE AC

400

320 - 0 % ... 440 + 0 %

45 ... 65

3/PE AC

500

400 - 0 % ... 550 + 0 %

45 ... 65

Voltage

Freq.

Current [A]

Current [A]

Number of

phases

[V]

[Hz]

c

max. +45° C

c

max. +55° C

E94AZMP0084

230/400/500

50/60

8/8/8

6/6/6

3

E94AZMP0294

230/400/500

50/60

29/29/29

21.8/21.8/21.8

3

E94AZMP0824

230/400/500

50/60

82/82/82

61/61/61

3

E94AZMP2004

230/400/500

50/60

200/200/200

150/150/150

3

c

Temperature in the control cabinet

Power loss

Inductance

Voltage drop

P

loss

[W]

L [mH]

Δ

U [V]

E94AZMP0084

50

3.9

9.8

E94AZMP0294

110

0.7

6.4

E94AZMP0824

200

0.25

6.4

E94AZMP2004

350

0.10

6.3

Thermal contact

Design

max. switching voltage

max. switching current

U

Th

[V AC]

I

Th

[A]

E94AZMP0084

NC contact, 150 °C

250

2.5

E94AZMP0294
E94AZMP0824

NC contact, 150 °C

250

2.5

E94AZMP2004

Fan

Voltage

Current

[V DC]

[A]

E94AZMP0824

24

0.3

E94AZMP2004