Rated data
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
LN
[V]
U
LN
[V]
f [Hz]
3/PE AC
230
180 - 0 % ... 264 + 0 %
45 ... 65
3/PE AC
400
320 - 0 % ... 440 + 0 %
45 ... 65
3/PE AC
500
400 - 0 % ... 550 + 0 %
45 ... 65
Voltage
Freq.
Current [A]
Current [A]
Number of
phases
[V]
[Hz]
c
max. +45° C
c
max. +55° C
E94AZMP0084
230/400/500
50/60
8/8/8
6/6/6
3
E94AZMP0294
230/400/500
50/60
29/29/29
21.8/21.8/21.8
3
E94AZMP0824
230/400/500
50/60
82/82/82
61/61/61
3
E94AZMP2004
230/400/500
50/60
200/200/200
150/150/150
3
c
Temperature in the control cabinet
Power loss
Inductance
Voltage drop
P
loss
[W]
L [mH]
Δ
U [V]
E94AZMP0084
50
3.9
9.8
E94AZMP0294
110
0.7
6.4
E94AZMP0824
200
0.25
6.4
E94AZMP2004
350
0.10
6.3
Thermal contact
Design
max. switching voltage
max. switching current
U
Th
[V AC]
I
Th
[A]
E94AZMP0084
NC contact, 150 °C
250
2.5
E94AZMP0294
E94AZMP0824
NC contact, 150 °C
250
2.5
E94AZMP2004
Fan
Voltage
Current
[V DC]
[A]
E94AZMP0824
24
0.3
E94AZMP2004