Safety instructions

Residual hazards

3

35

EDS94SPP101 EN 7.1

3.3

Residual hazards

Protection of persons

ƒ

Before working on the controller, check that no voltage is applied to the power

terminals, because
– depending on the controller - the power terminals U, V, W, +UG, -UG, Rb1 and Rb2

carry hazardous voltages for up to 3 to 20 minutes after mains disconnection.

– the power terminals L1, L2, L3; U, V, W, +UG, -UG, Rb1 and Rb2 carry hazardous

voltages when the motor is stopped.

Device protection

ƒ

Plug on or pull off all pluggable terminals only in deenergised condition!

ƒ

Detach the controllers only in deenergised conditions from their installation

backplanes or the back panel of the control cabinet!

ƒ

Cyclic switching on and off of the mains voltage can overload and destroy the input

current limitation of the controller:
– Cyclic mains switching of 5-times in 5 minutes is permissible without restrictions.

Motor protection

ƒ

Depending on the controller settings, the connected motor can be overheated by:
– For instance, longer DC-braking operations.
– Longer operation of self-ventilated motors at low speed.

Protection of the machine/system

ƒ

Drives can reach dangerous overspeeds (e.g. setting of high output frequencies in

connection with motors and machines unsuitable for such conditions):
– The controllers do not offer any protection against such operating conditions. Use

additional components for this purpose.