Single-axis controllers – Lenze 9400 Manual User Manual
Page 130
Single-axis controllers
Wiring
Devices in the range 145 ... 695 A (75 ... 370 kW)
4
130
EDS94SPP101 EN 7.1
Mains
Terminal X100
Marking
Description
Connection with ring
cable lug for M10
L1
L2
L3
Connection of the mains phases
SSP94KL801
Connection for the PE conductor on the supply side
Terminal data
Max. conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Device size 8:
E94ASxE1724
E94ASxE2024
2 x 240
2 x 500 mcm
19
168
WAF 16
Device size 9:
E94ASxE2454
E94ASxE2924
E94ASxE3664
Motor temperature monitoring
Terminal X106
Labelling
Description
T1
T2
Motor temperature monitoring with PTC element (type-A sensor,
switching performance according to EN 60947-8 for type-A tripping units)
or thermostat (NC contact).
SSP94X6106
Terminal data
Max. conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
2.5
12
0.5 ... 0.6
4.5 ... 6.2
Slot
0.6 x 3.5
With wire end ferrule