Multi-axis controllers

Wiring

Important notes

5

183

EDS94SPP101 EN 7.1

5.5

Wiring

5.5.1

Important notes

Danger!

Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains

disconnection.
Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Switch off the power supply and wait for at least three minutes before

working on the power terminals.

ƒ

Make sure that all power terminals are deenergised.

Danger!

Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800-5-1. Especially:

– Fixed installation

– PE connection must conform to standards (PE conductor diameter

10 mm

2

or PE conductor must be connected twice)

Stop!

The device contains components that can be destroyed by electrostatic

discharge!
Before working on the device, the personnel must ensure that they are free of

electrostatic charge by using appropriate measures.