Accessories (overview) – Lenze 9400 Manual User Manual

Page 364

Advertising
background image

Accessories (overview)

Communication modules

Ethernet interface

9

364

EDS94SPP101 EN 7.1

External voltage supply

Note!

Always use a separate power supply unit in every control cabinet and safely

separate it according to EN 61800-5-1 (”SELV”/”PELV”) in the case of external

voltage supply and larger distances between the control cabinets.

The external voltage supply of the communication module is required if EtherCAT

communication is to remain intact in case the supply of the standard device fails.
Supply the communication module via the 2-pole plug connector (X245) with a separate

supply voltage.

Designation

Description

+

External voltage supply

U = 24 V DC (20.4 V - 0 % ... 28.8 V + 0 %)

I = 130 mA

-

Reference potential for external voltage supply

Terminal data

Field

Values

Electrical connection

2-pin plug connector with spring connection

Possible connections

rigid:

1.5 mm

2

(AWG 16)

flexible:

without wire end ferrule

1.5 mm

2

(AWG 16)

with wire end ferrule, without plastic sleeve

1.5 mm

2

(AWG 16)

with wire end ferrule, with plastic sleeve

1.5 mm

2

(AWG 16)

Stripping length

9 mm

Advertising