Single-axis controllers, Control terminals – Lenze 9400 Manual User Manual
Page 141
Single-axis controllers
Control terminals
4
141
EDS94SPP101 EN 7.1
Terminal X2
Labelling
Description
GE
GND external supply
24E
24 V external supply via a safely separated power supply
unit (SELV/PELV) (only required for mains-independent supply of the
control electronics)
9400SSP000X2
SB
State bus in/out (reference GE)
Terminal data
Conductor cross-section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
0.2 ... 2.5
24 ... 12
Spring terminal
With wire end
ferrule
Electrical data
24 V
Rated voltage
24 V
According to IEC 61131-2
Voltage range
19.2 ... 28.8 V
Residual ripple max. ± 5 %
Current consumption
Approx. 1.2 A during operation
Max. 3 A starting current for 100 ms
Fuse
Circuit breaker with tripping
characteristic B or C,
Standard blade-type fuses
Looping through
Max. 12 devices with 2.5 mm
2
Fusing: 16/15 A
Max. 8 devices with 1.5 mm
2
Fusing: 10/10 A
Connectable cross-cuttings
See terminal data