1 operation at rated mains voltage 230 v, Operation at rated mains voltage 230 v, Power supply modules – Lenze 9400 Manual User Manual

Page 219: Input data, Output data

Advertising
background image

Power supply modules

Rated data (devices for 400/500V mains)

Operation at rated mains voltage 230 V

6

219

EDS94SPP101 EN 7.1

6.3.1

Operation at rated mains voltage 230 V

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

LN

[V]

U

LN

[V]

f [Hz]

3/PE AC

230

180 - 0 % ... 264 + 0 %

45 - 0 % ... 65 + 0 %

Input data

Voltage

Frequency

Current [A]

Number of

phases

[V]

[Hz]

max. +45 °C c

max. +55 °C c

E94APNE0104

230

50/60

8

6

3

E94APNE0364

230

50/60

29

21.8

3

E94APNE1004

230

50/60

82

61

3

E94APNE2454

230

50/60

200

150

3

c

Temperature in the control cabinet

Voltage

Continuous input power

Type

[V]

S

L

[kVA]

E94APNE0104

230

3.2

E94APNE0364

230

11.5

E94APNE1004

230

32.6

E94APNE2454

230

79.6

Output data

Basis of the data
Mains

Voltage

U

DC

[V]

Voltage range

U

DC

[V]

Frequency range

f [Hz]

2/PE DC

325

260 - 0 % ... 370 + 0 %

-

Voltage

Frequency

Current [A]

Number of

phases

[V]

[Hz]

max. +45 °C c

max. +55 °C c

E94APNE0104

325

0 (DC)

10

7.5

2

E94APNE0364

325

0 (DC)

36

27

2

E94APNE1004

325

0 (DC)

100

75

2

E94APNE2454

325

0 (DC)

245

184

2

c

Temperature in the control cabinet