Accessories (overview)

Communication modules

PROFIBUS

9

380

EDS94SPP101 EN 7.1

Wiring of the PROFIBUS

Observe the notes and wiring regulations given in the documentation for the

control system.

ƒ

Install a bus terminating resistor only at the first and last physical bus station.
– The bus terminating resistor is integrated into the bus connector and can be

activated via a switch.

– The bus terminator is fed by the bus station. When the communication module is

provided with an external power supply, ( 379) the bus terminator can be fed

independently from the power supply of the standard device.

ƒ

Check/activate the bus terminating resistors.

ƒ

Use the bus connector to connect the PROFIBUS with the controller.

ƒ

Only use cables which correspond to the listed specifications ( 381).

Note!

ƒ

The bus terminator must always be supplied. Otherwise, the bus can get

unstable.

ƒ

If you want to disconnect individual bus stations, ensure that the bus

terminators at the first and last physical bus station remain active.

ƒ

The bus terminator is no longer active if

– the connector has been pulled out e.g. in the event of service.

– the module supply has been switched off.

For further notes on the PROFIBUS network, please refer to the PROFIBUS

Communication Manual.